Reinforced Concrete Column Design Example

This example checks a tied reinforced concrete column to ACI 318-19 under an axial load and a moment. It checks the steel limits and slenderness, finds the strength by strain compatibility, and draws the interaction diagram. It also checks the shear and the ties. The column designer runs the same checks for every load combination.

The column

  • 16 in × 16 in, with eight #8 bars, three on each face, and #3 ties.
  • f′c = 4,000 psi, normal weight. Grade 60 bars, fy = 60,000 psi.
  • 1.5 in clear cover to the ties.
  • 12 ft clear height between floors, in a frame braced against sway by shear walls.
  • Factored loads: Pu = 420 kips, with end moments of 140 kip-ft at the top and 70 kip-ft at the bottom, bending it in double curvature.
Column cross section 16 by 16 inches with eight number 8 bars and number 3 ties 16 in × 16 in, 8 #8 bars #3 ties at 16 in, 1.5 in cover

The bars sit at 1.5 + 0.375 + 0.5 = 2.375 in from each face. In the direction of bending there are three layers: three bars at 2.375 in from the compression face, two at the middle (8 in) and three at 13.625 in.

Step 1: the steel limits

Ast = 8 × 0.79 = 6.32 in²    ρ = 6.32 / (16 × 16) = 2.47%

Columns need between 1% and 8% steel (10.6.1.1). Above about 4%, the bars get crowded at lap splices, so 2.47% is a comfortable amount.

Step 2: can slenderness be ignored?

For a braced column, take k = 1.0, which is conservative. The radius of gyration of a rectangle is about 0.3h (6.2.5.2):

k lu / r = 1.0 × 144 / (0.3 × 16) = 30

Slenderness can be ignored when this is no more than 34 + 12(M1/M2), and no more than 40 (6.2.5.1(b)). In ACI 318-19, M1/M2 is positive for double curvature, so 34 + 12 × (70 / 140) = 40. Since 30 ≤ 40, this is a short column, and the moments don't need to be magnified.

Step 3: the most axial load it can take

With no moment, the concrete and the steel both reach their full strength (22.4.2.2):

P0 = 0.85f′c(Ag − Ast) + fyAst = 0.85 × 4 × (256 − 6.32) + 60 × 6.32 = 848.9 + 379.2 = 1,228 kips

Every column has some accidental eccentricity, so ACI caps the design strength of a tied column at 80% of this, with φ = 0.65 (22.4.2.1):

φPn,max = 0.80 × 0.65 × 1,228 = 639 kips ≥ 420 kips    OK

Step 4: the moment strength at 420 kips

With a moment, the strength depends on where the neutral axis is. Choose a depth c, take the concrete strain as 0.003 at the compression face, and let the strain vary in a straight line. Each layer of bars has a strain ε = 0.003 (c − di) / c, and a stress Esε of no more than fy. Then add up the forces to get Pn, and their moments about the middle of the column to get Mn. Move c until φPn equals the load.

A few trials put the neutral axis at c = 11.26 in. The compression block is a = β1c = 0.85 × 11.26 = 9.57 in deep, and the concrete force is 0.85 × 4 × 9.57 × 16 = 520.8 kips, acting 9.57 / 2 = 4.79 in from the face.

PartDepth (in)StrainStress (ksi)Force (kips)Arm (in)Moment (kip-in)
Concrete0 to 9.573.4520.83.211,673
3 #8, top2.3750.0023760 − 3.4 = 56.6134.15.625754
2 #8, middle8.00.0008725.2 − 3.4 = 21.834.500
3 #8, bottom13.625−0.00063−18.3−43.2−5.625243
Total646.22,671

The top bars have yielded, since 0.00237 is past fy / Es = 0.00207. Bars inside the compression block have 0.85f′c = 3.4 ksi taken off, because the concrete they replace is already counted in the block. The bottom bars are in tension, but at a strain of only 0.00063. That is far below yield, so the section is compression-controlled and φ = 0.65 (Table 21.2.2).

φPn = 0.65 × 646.2 = 420 kips    φMn = 0.65 × 2,671 / 12 = 144.7 kip-ft ≥ Mu = 140 kip-ft    OK, at 97%

The interaction diagram

Repeating Step 4 for every depth of the neutral axis traces the column's interaction diagram: each axial load it can carry with the moment it can take at that load. Any load inside the design curve is safe.

Interaction diagram for the 16 by 16 inch column with eight number 8 bars, nominal and design strength, with the load point inside the design curve 0 50 100 150 200 250 300 0 200 400 600 800 1000 1200 Moment (kip-ft) Axial load (kips) Load: 420 k, 140 kip-ft balanced φPn,max = 639 k nominal, Pn and Mn design, φPn and φMn
  • The flat top is the 639 kip cap from Step 3.
  • The balanced point, where the concrete crushes just as the tension bars yield, is at φPn = 238 kips and φMn = 177 kip-ft. The nominal curve reaches its largest moment, 272 kip-ft, here.
  • Below the balanced point, the tension bars yield first and φ rises toward 0.90. That is why the design curve bulges out to its largest moment, 206 kip-ft, at about 100 kips. In this range, adding axial load helps the column take more moment.
  • Pure bending, at zero axial load, gives φMn = 172 kip-ft.

The load, 420 kips with 140 kip-ft, sits just inside the design curve.

Step 5: shear

The end moments change by 140 + 70 = 210 kip-ft over the 12 ft height, so Vu = 210 / 12 = 17.5 kips.

Axial compression adds to the concrete's shear strength. With at least the minimum ties (Table 22.5.5.1(a)), and Nu / 6Ag = 420,000 / (6 × 256) = 273 psi, capped at 0.05f′c = 200 psi:

Vc = (2λ√f′c + Nu / 6Ag) b d = (126.5 + 200) × 16 × 13.63 = 71.2 kips    φVc = 53.4 kips ≥ 17.5 kips    OK

The #3 ties at 16 in give Av/s = 0.22 / 16 = 0.0138 in²/in. That is more than the minimum 50b / fyt = 0.0133 in²/in, so the Table 22.5.5.1(a) equation applies.

Step 6: the ties

Tie spacing is the least of 16 bar diameters, 48 tie diameters and the column's smallest side (25.7.2.1):

s = min(16 × 1.0, 48 × 0.375, 16) = 16 in

Every corner bar has to sit in a corner of a tie, and no bar can be more than 6 in clear from a supported bar (25.7.2.3). The middle bar of each face is 5.625 − 1.0 = 4.6 in clear from the corner bars, so one square tie holds all eight bars, with no crossties.

The design

Column16 in × 16 in, f′c = 4,000 psi
Bars8 #8, ρ = 2.47%
Axial load and momentφMn = 144.7 kip-ft at 420 kips, against 140 kip-ft
ShearφVc = 53.4 kips against 17.5 kips
Ties#3 at 16 in, one square tie per set

The column works at 97% of its strength in bending, which leaves little room. If the loads could grow, #9 bars or 5,000 psi concrete would add margin.

Common mistakes

  • Using φ = 0.90 for a column. Most columns under real loads are compression-controlled, and φ = 0.65 for tied columns.
  • Forgetting the displaced concrete. Bars inside the compression block replace concrete that the block already counts.
  • The sign of M1/M2. ACI 318-19 flipped it from earlier editions: positive is now double curvature.
  • Checking only the largest moment. A lighter axial load with the same moment can be worse below the balanced point, so check every load combination.

Check it with the column designer

The column designer designs tied reinforced concrete columns to ACI 318-19 with WebStructural Pro. It finds the strength by strain compatibility, as in Step 4, with bending about both axes at once. It magnifies the moments of slender columns in braced and sway frames, and checks the shear, the ties and the steel limits for every load combination. For beams, see the reinforced concrete beam design example.

Frequently asked questions

What is a column interaction diagram?

A curve of every combination of axial load and moment that a column can carry. Each point comes from one position of the neutral axis. A load inside the design curve, which includes φ, is safe.

How much steel does a concrete column need?

Between 1% and 8% of its gross area (ACI 318-19 10.6.1.1). In practice, 1% to 4% keeps the bars from crowding at lap splices.

When is a concrete column slender?

In a braced frame, when klu/r is more than 34 + 12(M1/M2), up to 40. In a sway frame, when klu/r is more than 22. A slender column's moments are magnified for the extra bending caused by its deflection.

Why is φ 0.65 for tied columns?

A compression-controlled column fails suddenly, by the concrete crushing, with little warning. Spiral columns get 0.75 because the spiral holds the core together after the cover spalls.