Retaining Wall Designer
Cantilever, gravity and basement walls: overturning, sliding and bearing to IBC 1807.2.3, and the concrete to ACI 318-19.
Drag to turn, scroll or pinch to zoom. A wall that fails is red.
For a wall's footing on its own, the footing calculator; for bearing and SDS at an address, the site report.
Calculations
How the Retaining Wall Designer checks a wall
The designer checks a one-foot strip of wall. Pick the kind of wall, then click each tile to change its sizes, the soil and the loads. The wall is checked as you type, and a wall that doesn't work comes with the nearest one that does, which you can use with one click.
- Cantilever walls have a poured concrete or concrete block stem on a footing, with an optional key under the stem. Overturning and sliding need a safety factor of 1.5, or 1.1 with an earthquake (IBC 1807.2.3), with Rankine active pressure or an equivalent fluid pressure from a soils report, and passive pressure in front with the top foot left out. The soil under the footing is checked against the allowable bearing, with the resultant kept in the middle third. The stem, toe, heel and key bars are designed by ACI 318-19 strength design, with the soil pressure factored by 1.6. Block stems are checked to TMS 402.
- Gravity walls are plain concrete, wider at the bottom, held by their own weight and the soil on their sloped back. The stem and footing are checked as plain concrete by ACI 318-19 Chapter 14.
- Basement walls span from the slab to the floor framing, with the soil pushing at rest (K0 = 1 − sin φ). The wall is checked for bending, shear and the floor load with the bending, and the reactions the floor and slab must hold are given.
- Water behind the wall adds its own pressure, makes the soil below it lighter, and pushes up under the footing. Earthquakes add soil pressure of 3/8 kh γ H² at 0.6H (Seed and Whitman), with kh = SDS / 2.5, and shake the wall and the soil on the heel.
Not checked: global stability (a slope failure that passes below the wall), settlement, and walls braced at the top other than basement walls. Have a geotechnical engineer look at a wall on a slope, on soft soil or over about 6 ft. The results are a design aid: have a licensed engineer check a design before it's built.
Retaining wall sizes by height
The least concrete that works for each height of level backfill with no surcharge. Click a height to open that wall in the designer, then change it to suit your site.
Cantilever retaining wall footings
In soil weighing 120 pcf with a 30° friction angle, 0.35 sliding friction, 150 pcf passive pressure and 1,500 psf allowable bearing, with the footing 1′ below the ground in front and 3,000 psi concrete. Sliding sets the width of most of these walls; firmer soil or a deeper footing makes them narrower. The stem bars are vertical, on the backfill side, hooked into the footing.
| Retained height | Stem | Stem bars | Footing | Width | Toe | Heel |
|---|---|---|---|---|---|---|
| 2′ | 8 in | #4 at 13 in | 12 in | 2′ 3″ | 0′ 9″ | 0′ 10″ |
| 3′ | 8 in | #4 at 13 in | 12 in | 3′ | 1′ | 1′ 4″ |
| 4′ | 8 in | #4 at 13 in | 12 in | 4′ | 1′ 3″ | 2′ 1″ |
| 5′ | 8 in | #4 at 13 in | 12 in | 5′ 3″ | 1′ 9″ | 2′ 10″ |
| 6′ | 8 in | #4 at 13 in | 12 in | 6′ 3″ | 2′ | 3′ 7″ |
| 7′ | 8 in | #4 at 11 in | 12 in | 7′ 6″ | 2′ 6″ | 4′ 4″ |
| 8′ | 8 in | #4 at 8 in | 12 in | 8′ 6″ | 2′ 9″ | 5′ 1″ |
| 9′ | 10 in | #4 at 8 in | 12 in | 9′ 9″ | 3′ 3″ | 5′ 8″ |
| 10′ | 8 in | #5 at 6 in | 16 in | 10′ 9″ | 3′ 6″ | 6′ 7″ |
Gravity retaining walls
Plain concrete with a 12 in top, a 0′ 6″ toe and heel, and the stem's back sloping out to the bottom width. Sand weighing 120 pcf with a 30° friction angle, 0.35 sliding friction, 150 pcf passive pressure and 2,000 psf allowable bearing (IBC Table 1806.2), and 2,500 psi concrete.
| Retained height | Stem top | Stem bottom | Footing | Width | Toe | Heel |
|---|---|---|---|---|---|---|
| 2′ | 12 in | 1′ 3″ | 12 in | 2′ 3″ | 0′ 6″ | 0′ 6″ |
| 3′ | 12 in | 1′ 9″ | 12 in | 2′ 9″ | 0′ 6″ | 0′ 6″ |
| 4′ | 12 in | 2′ 6″ | 12 in | 3′ 6″ | 0′ 6″ | 0′ 6″ |
| 5′ | 12 in | 3′ 3″ | 12 in | 4′ 3″ | 0′ 6″ | 0′ 6″ |
| 6′ | 12 in | 4′ | 12 in | 5′ | 0′ 6″ | 0′ 6″ |
| 7′ | 12 in | 4′ 6″ | 12 in | 5′ 6″ | 0′ 6″ | 0′ 6″ |
| 8′ | 12 in | 6′ 3″ | 12 in | 7′ 3″ | 0′ 6″ | 0′ 6″ |
Basement wall bars by soil height
Vertical bars 1.5 in from the inside face, for drained soil weighing 120 pcf with a 30° friction angle (at rest, the same as 60 pcf of fluid pressure), no surcharge, 500 lb/ft dead and 300 lb/ft live load from the floor, and 3,000 psi concrete.
| Soil height | 8 in wall, 8′ tall | 8 in wall, 9′ tall | 10 in wall, 9′ tall | 10 in wall, 10′ tall |
|---|---|---|---|---|
| 4′ | #4 at 18 in | #4 at 18 in | #4 at 16 in | #4 at 16 in |
| 5′ | #4 at 18 in | #4 at 18 in | #4 at 16 in | #4 at 16 in |
| 6′ | #4 at 18 in | #4 at 18 in | #4 at 16 in | #4 at 16 in |
| 7′ | #4 at 18 in | #4 at 18 in | #4 at 16 in | #4 at 16 in |
| 8′ | #4 at 16 in | #4 at 15 in | #4 at 16 in | #4 at 16 in |
| 9′ | – | #4 at 14 in | #4 at 16 in | #4 at 15 in |
| 10′ | – | – | – | #4 at 13 in |
Soils vary more than these walls do. Heavier soil, water, a sloped backfill or a surcharge takes more; check your own wall above.
Retaining wall questions
How wide should a retaining wall footing be?
Usually from half to the full height of the wall, measured from the bottom of the footing to the top of the soil. Loose or wet soil, sloped backfill and a surcharge all push it wider. About a third of the width goes in front of the stem and the rest behind it, where the soil on the heel helps hold the wall up.
What soil values do I use without a soils report?
IBC Table 1806.2 gives presumptive values: 1,500 psf bearing and 100 pcf passive pressure for clay and silt, 2,000 psf and 150 pcf for sand, and 3,000 psf and 200 pcf for sandy gravel. Sliding friction is 0.25 for sand and 0.35 for gravel. Clay resists sliding with 130 psf of cohesion instead, which the designer doesn't count, so use 0.25 or less on clay. A friction angle of 30° and 120 pcf soil are typical for clean sand and gravel backfill. The site report gives the soil and SDS at an address.
Why does my wall slide?
Sliding sets the width of most walls. Widen the heel to put more soil on the footing, set the footing deeper so more soil sits in front of it, or add a key: a short wall of concrete under the stem that digs into the soil, so the soil in front of it pushes back. Keys are usually 12 in wide and 12 to 24 in deep. When a wall fails, the designer offers one with a key if that makes the footing much narrower.
What is a gravity retaining wall, and how tall can it be?
A wall that holds back soil by its own weight, with no bars: plain concrete, wide at the bottom and narrower at the top, with the bottom usually half to two thirds of the full height. Concrete gravity walls are common up to about 6 to 8 ft of retained soil, and the designer goes to 10 ft. Above that, a cantilever wall uses much less concrete. Sloping the back instead of the front puts the soil's weight on the wall, which helps against overturning and sliding.
Why does a basement wall take more pressure than a retaining wall?
A retaining wall leans away from the soil a little, which lets the soil settle into its lower, active pressure. A basement wall can't, because the floor holds its top, so the soil stays at rest and pushes about half again as hard: 60 pcf of fluid pressure instead of 40 for typical sand. The bars go near the inside face, which the soil stretches. Backfill only after the slab is poured and the floor is framed, or brace the wall.
Does the wall need drainage?
Yes. Water behind a wall can double the pressure on it. Put free-draining gravel against the back of the wall with a perforated drain along the footing, or weep holes through it, so the soil stays drained. If water can rise behind the wall anyway, enter its level and the designer counts it.