Diaphragm Calculator

Check a wood roof or floor diaphragm: enter its span between the shear walls, its depth, the sheathing and nailing, and the wind and earthquake load, and see whether the sheathing carries the load to the walls and how far it bends. Pro adds the chord forces, where the nailing can step down, and a PDF report.

The roof or floor

Across the load, wall to wall
Along the load, chord to chord
Case 1: no unblocked edges or continuous joints along the load

Wind (strength level)

Whole-building pressure, windward plus leeward; 16 at least
Half the wall below plus the wall or roof above

Earthquake (strength level)

From the ASCE Hazard Tool; 0 for none
The roof or floor, plus the walls hanging off it, per square foot
I or II for most houses
Usually the double top plate

The diaphragm works with 15/32 in Rated sheathing, 8d nails, 2x framing, blocked, 6 in at boundaries, 6 in at panel edges, using 17% of its capacity (limited by wind).

Shear at the ends

Wind0.6 × 20 psf × 8′ = 96 plf; 64 plf at the ends on 378 plf allowed 17% PASS
Earthquake0.7 × 0.100 × 20 psf × 30′ = 42 plf; 28 plf at the ends on 270 plf allowed 10% PASS

Allowable unit shear 270 plf from the table for earthquakes, 1.4 times for wind. Span over depth 1.33, at most 4.

15/32 in Rated sheathing, 8d nails, 2x framing

Blocked, 6 in at boundaries, 6 in at panel edges 17%
Blocked, 4 in at boundaries, 6 in at panel edges 13%
Blocked, 2-1/2 in at boundaries, 4 in at panel edges 9%
Blocked, 2 in at boundaries, 3 in at panel edges 8%
Unblocked, case 1, 6 in at supported edges 19%
Unblocked, cases 2 to 6, 6 in at supported edges 25%

Deflection at midspan

Wind, at 0.6Wchords 0.01 in, sheathing 0.01 in, nail slip 0.00 in0.01 in
Earthquake, at strength levelchords 0.00 in, sheathing 0.00 in, nail slip 0.00 in; times Cd 4 = 0.03 in toward the story drift0.01 in

OSB panels, (2) 2x4 chords, no slip at chord splices. The code sets no limit; keep it small enough that the walls the diaphragm pushes on can follow it.

Chords and nailing zones Pro

The tension and compression in the chords along the diaphragm's edges, how far in from each end the heavier nailing has to run before lighter nailing takes over, and a PDF report of the whole diaphragm.

Wind 20 psf on 8′ of building face; earthquake Fpx = 0.2 SDS Ie = 0.100 times 20 psf, risk category I or II, both at strength level. A simple span between two shear walls under a uniform load, nailed with common nails into dry framing. Collectors, openings in the diaphragm and the shear walls aren't checked.

Allowable unit shear for wood diaphragms

Pounds per foot at allowable stress for earthquakes, with 2x framing of Douglas Fir-Larch or Southern Pine and common nails. Blocked columns give the nail spacing at the boundaries and continuous panel edges over the spacing at the other panel edges, in inches. Wind takes 1.4 times these; 3x framing takes about 10% more.

SheathingBlocked 6 / 6Blocked 4 / 6Blocked 2½ / 4Blocked 2 / 3Unblocked case 1Unblocked cases 2–6
5/16 in Structural I, 6d nails185250375420165125
3/8 in Structural I, 8d nails270360530600240180
15/32 in Structural I, 10d nails320425640730285215
5/16 in Rated sheathing, 6d nails170225335380150110
3/8 in Rated sheathing, 6d nails185250375420165125
3/8 in Rated sheathing, 8d nails240320480545215160
7/16 in Rated sheathing, 8d nails255340505575230170
15/32 in Rated sheathing, 8d nails270360530600240180
15/32 in Rated sheathing, 10d nails290385575655255190
19/32 in Rated sheathing, 10d nails320425640730285215

Hem-Fir framing takes 0.93 of these, Spruce-Pine-Fir 0.92.

How the calculator checks a diaphragm

A diaphragm is a roof or floor sheathed with plywood or oriented strand board (OSB) that carries the wind or earthquake load sideways to the shear walls. It acts like a deep beam lying flat: the sheathing takes the shear and the chords along its edges, usually the double top plates, take the bending. The calculator follows the Special Design Provisions for Wind and Seismic (SDPWS) 2021 with allowable stress design (ASD):

  • Loads: the wind on the building face the diaphragm holds up, at strength level, times 0.6; and the diaphragm earthquake force Fpx = 0.2 SDS Ie times its weight, times 0.7 (ASCE 7 12.10.1.1). That is the least Fpx can be, and it governs for a one-story building; the roof of a taller building can take up to twice as much.
  • Shear: a simple span between two shear walls under a uniform load w: the unit shear at each end is wL / 2b. It has to stay within the sheathing's allowable unit shear from the table above, adjusted for lighter framing species.
  • Shape: the span over the depth is at most 4 for a blocked diaphragm and 3 for an unblocked one (SDPWS Table 4.2.4).
  • Deflection: the four-part equation from the SDPWS commentary, without chord splice slip: the chords stretching and squashing, the sheathing straining in shear, and the edge nails slipping, at midspan. An unblocked diaphragm bends 2.5 times as far as a blocked one. Sheathing rigidity comes from IBC Table 2305.2(2) and nail slip from the SDPWS commentary for dry framing.
  • Chords (Pro): the force in each chord at midspan is wL2 / 8b, tension on one edge and compression on the other.
  • Nailing zones (Pro): the shear drops to nothing at midspan, so lighter nailing can take over where the shear is within its capacity.

Not checked: collectors and drag struts, openings in the diaphragm, diaphragms that cantilever or have more than two supporting walls, chord splices, and the shear walls themselves (the shear wall calculator checks those).

Diaphragm questions

Which way is the span?

The span runs between the two shear walls that hold the diaphragm up, across the direction the load pushes. The depth runs along the load, from one chord to the other. Check each direction of a building separately: the wind on the long side spans the diaphragm between the end walls, and the wind on the end spans it between the side walls.

Blocked or unblocked?

Blocking puts framing under every panel edge so the edges can be nailed all round. Unblocked roofs are cheaper and often enough for a house. Case 1 is panels with their continuous joints running across the load; the other layouts carry about a quarter less. Above about 3 times as long as deep, a diaphragm has to be blocked.

What weight do I enter?

The roof or floor dead load in pounds per square foot, plus the weight of the walls that hang off it (half the height of the walls below, and the walls above for a floor), spread over the diaphragm's area. A light roof with its walls is often 15 to 25 psf.

What are the chords?

The members along the two edges that run the length of the span, usually the double top plates of the walls. They take the diaphragm's bending as tension and compression, so their splices have to be nailed or strapped for that force. Choose (2) 2x4, (3) 2x4, (2) 2x6, (3) 2x6 for the deflection.