Concrete Slab Designer
Reinforced concrete one-way slabs, two-way slabs on walls and flat plates on columns, to ACI 318-19, and slabs on ground or on foam insulation.
Results
Drag to turn, scroll or pinch to zoom. Red: bottom bars. Orange: top bars.
Calculations
How thick should a concrete slab be?
ACI 318-19 sets a minimum thickness for each kind of slab. A slab at least this thick doesn't need its deflection worked out, unless it carries partitions or finishes that crack. These are the minimums for normal weight concrete and grade 60 bars, rounded up to the next 1/4 in.
One-way slabs (ACI Table 7.3.1.1)
| Span, center to center | Simply supported (l/20) | One end continuous (l/24) | Both ends continuous (l/28) | Cantilever (l/10) |
|---|---|---|---|---|
| 6 ft | 3.75 in | 3 in | 2.75 in | 7.25 in |
| 8 ft | 5 in | 4 in | 3.5 in | 9.75 in |
| 10 ft | 6 in | 5 in | 4.5 in | 12 in |
| 12 ft | 7.25 in | 6 in | 5.25 in | 14.5 in |
| 14 ft | 8.5 in | 7 in | 6 in | 17 in |
| 16 ft | 9.75 in | 8 in | 7 in | 19.25 in |
| 18 ft | 11 in | 9 in | 7.75 in | 21.75 in |
| 20 ft | 12 in | 10 in | 8.75 in | 24 in |
Flat plates (ACI Table 8.3.1.1)
| Clear span, long way | Exterior panel, no edge beam (ln/30) | Interior panel (ln/33) |
|---|---|---|
| 12 ft | 5 in | 5 in |
| 14 ft | 5.75 in | 5.25 in |
| 16 ft | 6.5 in | 6 in |
| 18 ft | 7.25 in | 6.75 in |
| 20 ft | 8 in | 7.5 in |
| 22 ft | 9 in | 8 in |
| 24 ft | 9.75 in | 8.75 in |
| 26 ft | 10.5 in | 9.5 in |
| 28 ft | 11.25 in | 10.25 in |
| 30 ft | 12 in | 11 in |
Flat plates are at least 5 in. The clear span is face to face of the columns.
How the Concrete Slab Designer checks a slab
Every slab is designed per foot of width with its own weight at 150 pcf plus the dead load, and the live load, factored by 1.2 and 1.6 (or 1.4 times the dead load alone, if that's more), with grade 60 bars by the American Concrete Institute's ACI 318-19. No finite element model is needed: each kind of slab has a closed-form method.
- One-way slabs: one span by statics, or two or more equal spans by the ACI moment and shear coefficients (Table 6.5.2), which apply when the live load is no more than three times the dead load. The bars meet the minimum steel, spacing and crack control limits, with shrinkage and temperature bars across the span.
- Two-way slabs on walls: elastic plate theory for a slab simply supported on four edges (Navier's series, as ACI 8.2.1 allows), giving the moment each way and the deflection at the center.
- Flat plates: the direct design method (ACI 8.10) for at least three equal spans each way, with the moment shared between the supports and midspan, then between the column and middle strips. Punching shear is checked at an interior, an edge and a corner column, with the share of the slab's moment each column takes by shear.
- Slabs on ground or foam: the slab as a plate on springs, by Westergaard's equations, with rigid foam insulation and the soil under it as two springs, one on the other. A wheel and a floor jack are each checked away from the edges, at a free edge and at a free corner: the concrete's bending stress against its modulus of rupture over a safety factor (2.0 for wheels, 1.5 for a jack), and the pressure on the foam against a share of its compressive strength. The bars are checked for shrinkage by subgrade drag, and the joints for spacing (ACI 360R and 302.1R).
- Shear: one-way shear without stirrups by ACI 22.5.5.1(c), with the size effect and the steel ratio, at d from the support.
- Deflection: for one-way slabs and slabs on walls, worked out with the effective moment of inertia of ACI 24.2.3.5, a long-term creep factor of 2.0 and the limits of Table 24.2.2. Flat plates must meet the minimum thickness instead.
Anyone can check the minimum thickness. Pro adds the bars top and bottom, every check worked out with its ACI section, saved designs in projects and folders, and PDF reports.
Not covered: cantilevers, drop panels and edge beams, openings, unequal spans, point loads, and wind or earthquake loads on the slab.
Concrete slab questions
Is my slab one-way or two-way?
A slab held on two opposite sides spans one way. One held on all four sides spans both ways, unless it's more than twice as long as it is wide: then nearly all its load goes the short way, and it acts like a one-way slab.
Can a concrete slab go on foam insulation?
Yes, and energy codes now often ask for insulation under slabs. Rigid foam is much softer than soil, so the slab bends a little more under a wheel, but it spreads the load so far that the foam feels only a few psi. Check the foam's compressive strength at 10% strain on its data sheet: under repeated wheel loads keep the pressure under about a fifth of it. A floor jack at a joint or edge is usually the hardest load on the concrete.
What is punching shear?
Around a column, a flat plate can fail by the column pushing through it, tearing out a cone of concrete. It usually decides how thick a flat plate must be, most often at the corner and edge columns. A thicker slab, a bigger column, drop panels or shear studs fix it.
What's the difference between the column strip and the middle strip?
In a flat plate the slab near the column lines is stiffer and takes more of the moment. ACI splits each panel into a column strip a quarter of the shorter span each side of the column line, and the middle strip between, and gives the column strip 60% to 100% of the moment.