Concrete Slab Designer

Reinforced concrete one-way slabs, two-way slabs on walls and flat plates on columns, to ACI 318-19, and slabs on ground or on foam insulation.

Slab

The longest distance between saw cuts or edges.

All the same length.

Square columns.

Normal weight, grade 60 bars.

Sets the cover.

One layer, for shrinkage cracks.

From the bottom of the slab to the bottom of the bars.

Foam and ground

Compressive strength at 10% strain, ASTM D1621, from the data sheet. 0 for no foam.

Modulus of subgrade reaction: about 50 for soft clay, 100 to 200 for compacted soil, 200 to 300 on a compacted gravel base.

Loads

Finishes, ceiling and partitions, besides the slab's own weight.

40 for homes, 50 for offices, 100 for corridors.

A quarter of the vehicle's weight, or more on its heavier axle.

The wheel load over the tire pressure: 2,000 lb at 40 psi is 50 in².

What it lifts: about half the vehicle at the middle of an axle, less at a corner. 0 for none.

Its small steel wheels or stand feet: often 2 to 6 in².

Sets the deflection limit.

Results

Drag to turn, scroll or pinch to zoom. Red: bottom bars. Orange: top bars.

How thick should a concrete slab be?

ACI 318-19 sets a minimum thickness for each kind of slab. A slab at least this thick doesn't need its deflection worked out, unless it carries partitions or finishes that crack. These are the minimums for normal weight concrete and grade 60 bars, rounded up to the next 1/4 in.

One-way slabs (ACI Table 7.3.1.1)

Span, center to centerSimply supported (l/20)One end continuous (l/24)Both ends continuous (l/28)Cantilever (l/10)
6 ft3.75 in3 in2.75 in7.25 in
8 ft5 in4 in3.5 in9.75 in
10 ft6 in5 in4.5 in12 in
12 ft7.25 in6 in5.25 in14.5 in
14 ft8.5 in7 in6 in17 in
16 ft9.75 in8 in7 in19.25 in
18 ft11 in9 in7.75 in21.75 in
20 ft12 in10 in8.75 in24 in

Flat plates (ACI Table 8.3.1.1)

Clear span, long wayExterior panel, no edge beam (ln/30)Interior panel (ln/33)
12 ft5 in5 in
14 ft5.75 in5.25 in
16 ft6.5 in6 in
18 ft7.25 in6.75 in
20 ft8 in7.5 in
22 ft9 in8 in
24 ft9.75 in8.75 in
26 ft10.5 in9.5 in
28 ft11.25 in10.25 in
30 ft12 in11 in

Flat plates are at least 5 in. The clear span is face to face of the columns.

How the Concrete Slab Designer checks a slab

Every slab is designed per foot of width with its own weight at 150 pcf plus the dead load, and the live load, factored by 1.2 and 1.6 (or 1.4 times the dead load alone, if that's more), with grade 60 bars by the American Concrete Institute's ACI 318-19. No finite element model is needed: each kind of slab has a closed-form method.

  • One-way slabs: one span by statics, or two or more equal spans by the ACI moment and shear coefficients (Table 6.5.2), which apply when the live load is no more than three times the dead load. The bars meet the minimum steel, spacing and crack control limits, with shrinkage and temperature bars across the span.
  • Two-way slabs on walls: elastic plate theory for a slab simply supported on four edges (Navier's series, as ACI 8.2.1 allows), giving the moment each way and the deflection at the center.
  • Flat plates: the direct design method (ACI 8.10) for at least three equal spans each way, with the moment shared between the supports and midspan, then between the column and middle strips. Punching shear is checked at an interior, an edge and a corner column, with the share of the slab's moment each column takes by shear.
  • Slabs on ground or foam: the slab as a plate on springs, by Westergaard's equations, with rigid foam insulation and the soil under it as two springs, one on the other. A wheel and a floor jack are each checked away from the edges, at a free edge and at a free corner: the concrete's bending stress against its modulus of rupture over a safety factor (2.0 for wheels, 1.5 for a jack), and the pressure on the foam against a share of its compressive strength. The bars are checked for shrinkage by subgrade drag, and the joints for spacing (ACI 360R and 302.1R).
  • Shear: one-way shear without stirrups by ACI 22.5.5.1(c), with the size effect and the steel ratio, at d from the support.
  • Deflection: for one-way slabs and slabs on walls, worked out with the effective moment of inertia of ACI 24.2.3.5, a long-term creep factor of 2.0 and the limits of Table 24.2.2. Flat plates must meet the minimum thickness instead.

Anyone can check the minimum thickness. Pro adds the bars top and bottom, every check worked out with its ACI section, saved designs in projects and folders, and PDF reports.

Not covered: cantilevers, drop panels and edge beams, openings, unequal spans, point loads, and wind or earthquake loads on the slab.

Concrete slab questions

Is my slab one-way or two-way?

A slab held on two opposite sides spans one way. One held on all four sides spans both ways, unless it's more than twice as long as it is wide: then nearly all its load goes the short way, and it acts like a one-way slab.

Can a concrete slab go on foam insulation?

Yes, and energy codes now often ask for insulation under slabs. Rigid foam is much softer than soil, so the slab bends a little more under a wheel, but it spreads the load so far that the foam feels only a few psi. Check the foam's compressive strength at 10% strain on its data sheet: under repeated wheel loads keep the pressure under about a fifth of it. A floor jack at a joint or edge is usually the hardest load on the concrete.

What is punching shear?

Around a column, a flat plate can fail by the column pushing through it, tearing out a cone of concrete. It usually decides how thick a flat plate must be, most often at the corner and edge columns. A thicker slab, a bigger column, drop panels or shear studs fix it.

What's the difference between the column strip and the middle strip?

In a flat plate the slab near the column lines is stiffer and takes more of the moment. ACI splits each panel into a column strip a quarter of the shorter span each side of the column line, and the middle strip between, and gives the column strip 60% to 100% of the moment.